SIGNAL-20P DESIGN AND OPERATING PRINCIPLES
31
Program name Program description Initial
status
36
"Turn on with
temperature
increasing"
If an alarm loop has entered “High tem-
perature” status**, that is, the tempera-
ture has exceeded "temperature high"
threshold then switches ON
OFF
37
"Turn on with
temperature
decreasing"
If an alarm loop has entered “Low tem-
perature” status**, that is, the tempera-
ture has exceeded "temperature low"
threshold then switches the relay ON
OFF
Remarks:
* - The relay status is defined by the statuses of assigned loops
** - Only programmable auxiliary alarm loop (type 12) can enter the statuses
“Temperature High” or “Temperature Low” and only if these statuses are
programmed for this loop
Table 6: The correspondence between the output minus lead
voltage and the status of the outer circuit
Norm Open failure Short failure
Output is
on
Output is
off
Output is
on
Output is
off
The output voltage is
within the range from
0,35V to 4,0V
less then
0,05 V
more than
4,1 V
more than
4,5 V
less then
0,3 V
4.3 Settings
The device settings specify its operating in whole and give the net
settings when operating in network mode as the part of the Orion safety
system. They are presented by the Table 8.
Table 7: The device settings
Parameter Description Range
Voltage Analysis
Defines the method of the transi-
tion to the “Power Failed” mode in
case of one or two input power
supplies having been out of range
On / Off
Net Address
Gives the net device address
when connecting to the RS-485
interface
1…127