SIGNAL-20P APPLICATION
35
5 APPLICATION
5.1 Preparation
5.1.1 Protective measures
There are no dangerous voltage circuits within the device.
The mounting and maintaining of the device shall be executed under
power–off conditions.
5.1.2 Device mounting
The device can be mounted to the wall or to other places on prem-
ises being protected from atmospheric fallouts and mechanical damages.
The installation procedure is as follows:
a) Attach the device to the wall in any convenient place. If the de-
vice is housed at unwatched premises place it at least 2,2 m
higher from the floor level
b) Attach the connecting wires in accordance with the connecting
diagram presented in Appendix C
c) Connect the isolating diodes for "К4" and "К5" outputs as close
to the visible or audible alarm terminals as possible. If these out-
puts are not in use stub its by 1 kОhm/0,25 W resistor
5.1.3 RS-485 interface wiring
To connect the device to the net controller via RS-485 highway inter-
face execute the following steps:
a) Connect the A and B lines of RS-485 highway interface to the "A"
and "B" terminals of device
b) Connect the device circuit "0B" to the similar circuits of preceding
and following RS-485 connected devices (it is not obligatory if the devices
are connected to the same power supply)
c) If the device is neither first nor last one into the interface line then
delete the jumper being located closely to the "A" and the "B" terminals of
the device and connecting the 620 Ohm terminal resistor to the interface
line.
When wiring the RS-485 interface it should connect the devices in se-
ries (into the bus configuration). If it is necessary to make long RS-485 in-
terface branch (longer than 50 m), for example, to reduce the cable length,
it is recommended to use the interface repeater S2000-PI. One can use no
more than 10 repeaters (no more than 10 interface branches) in one RS-
Vista de página 34