Signal-10 Specifications
11 www.bolid.com
¾ Alarm Inputs
10 inputs to monitor alarm loops
Detectors to Be Included
Addressable initiating devices DIP-34PA, IPR513-3PA,
S2000-IP-PA (up to 10 to each alarm input), or
any conventional fire and intrusion detectors intended
to be powered by a DC power supply and having the
values of internal resistance at Fire mode:
No more than 2.7 kΩ for normally open detectors,
At least 3.2 kΩ for normally closed detectors
Max Wire Resistance
(without regard to termination resistor)
1 kΩ for intrusion alarm loops,
100 Ω for fire alarm loops
Min Leakage Resistance Between
Loop Wires or Between Each Wire
and the Earth
20 kΩ for intrusion alarm loops,
50 kΩ for fire alarm loops
Loop Voltage
22 V÷ 19 V if the termination resistor of 4.7 kΩ±5% is
brought to the loop and the value of consumed current
is 0 to 3 мА (provided that there are no more than 3
short-circuited loops simultaneously,
27 ± 0.5 V if the alarm loop is opened
Max.Short-Circuited Loop Current
26.5 mА
Loop Ripple Voltage
20 mV max
¾ Solid State Relay Outputs
Commuting Voltage & Current
2 outputs ALR1 and ALR2 with normally open contacts
intended to transmit alarms and troubles to Central
Stations
170 V dc & 0.1 А; 130 V ac & 0.1 А
¾ Transistor Outputs
Commuting Voltage & Current
Load Circuit Supervision Current
Load Circuit Protection
2 outputs with the possibilities to supervise load circuits
for open and short failures; these outputs are intended
to connect external sound and light alarms
28 V & 1 А
3 mА max, the alarms being off
Resettable fuses
¾ Operating Temperatures
From 30 °С to +50 °С