RELAY OUTPUTS
The Signal-10 device is equipped with four executive outputs, among them
¾ Two solid state relays ALR1 and ALR2 with normally open contacts, galvanic isolation, and
switching capacity of 170 V dc / 0.1А or 130 V ac / 0.1А, and
¾ Two transistor outputs SIR and LAM with output switching capacity of 28V/1А which can be
monitored for load circuit troubles and provide overcurrent protection by means of resettable
fuses
The SIR and LAM outputs are usually used to connect external sound and light alarms indicating
alarms and troubles. Outputs ALR1 and ALR2 are intended for separate transmission of fire alarms and
troubles in fire safety systems, or for transmission fire and intrusion alarms to central guard stations,
central monitoring stations, fire brigades, and so on. Optionally the relay outputs can be adapted to
meet individual user requirements, for example, to unset power of four wire detectors before its will be
armed, or to turn on/off various technical equipment (such as heaters, coolers, ventilators, air condi-
tioners, etc.) in case of alarm loops of Type 12 status altering.
Table 3 shows the programmable parameters of Signal-10 outputs.
Table 3. Signal-10 Outputs Configuration Parameters
Parameter Description Value Range
Executive
Program
Defines the initial relay on/off condition and
the way the output will be controlled depend-
ing on the status of the alarm loops related
with this output
1 ... 37
Relay
Activation Time
Defines the time interval for which the relay
will be switched on/off if the assigned execu-
tive program implies the limited activation
time
0 s to 8192 s
(up to 2 hours 16 minutes 32s)
in increments of 0.125 s
Relay ON/OFF
Events
Enables/disables event transmissions in case
of output on/off condition altering in order to
display on system indicator modules or to log
these events in system database
On / Off
Monitor For
Defines the load circuit monitoring tactics for
outputs SIR (the relay 3) and LAM
(the relay 4)
1 – Without Monitoring
2 – Open Failure
3 – Short Failure
4 – Open and Short Failure
The Signal-10 outputs ALR1, ALR2, SIR, and LAM can be controlled in two ways:
Locally in accordance with an assigned executive program depending on statuses of related
alarm loops (see below)
Remotely by network controller commands