Signal-10 Programming
79 www.bolid.com
PROGRAMMING OUTPUTS
To program the Signal-10 relay outputs, use Outputs Tab of the UProg Configuration Tool (see
Figure 15).
If one of the device relays is to be centrally-controlled by network controller commands than this relay
must not be related with any device alarm loop (the relative Relay…Control parameter must be set off
for all the device alarm loops see above).
If, otherwise, a relay is to be controlled locally depending on the device alarm loop statuses, the relay
must be related to the relevant alarm loops via the relative Relay…Control parameter. Moreover, a
relay activation delay can be specified at the Alarm Loops tab see the previous section.
NOTE: If a relay is assigned to an alarm loop (loops) then control commands of a network con-
troller via RS-485 highway will be ignored. Local relay control is more priority than cen-
tralized one.
Figure 15. Signal-10 Relay Outputs Programming