Table 7. Programmable Auxiliary Loops Available Statuses
Status
Code
Status
Status
Code
Status
1 AC Power Restored 77 Too Low Level
2 AC Power Failed 78 Normal Temperature
3 Intrusion Alarm 82 Heat Sensor Failed
17 Arming Failed 109 Disarmed
24 Armed 118 Entrance Alarm
35 Auxiliary Zone Restored 130 Pump On
36 Auxiliary Zone Alarm 131 Pump Off
37 Fire Alarm 149 Tamper Alarm
38 Auxiliary Zone Alarm-2 152 Tamper Restored
39 Fire Equipment Restored 198 Power Failed
41 Fire Equipment Trouble 199 Power Restored
44 Fire Prealarm 200 Battery Restored
45 Loop Open Failure 202 Battery Failed
58 Panic Alarm 204 Service Required
71 Low Level 206 Low Temperature
72 Normal Level 214 Loop Short Failure
74 High Level 216 Fire Signal
75 Too High Level 220 Gas Press Signal
76 High Temperature 223 Patrol Check
While programming resistance thresholds for statuses of an alarm loop of the Type 12, it needs to know
strictly the resistance range for each of the loop status. As it is quite a difficult task, the actual alarm
loop resistances can be approximately calculated based on resistance values expressed in ACD units
and measured by the Signal-10 device using the formula:
1
281
loop
=
ADC
R , [KΩ],
where R
loop
is the actual resistance value of an alarm loop and
ADC is the ADC-value of the resistance measured by the Signal-10 device.
This formula enables adequately calculating resistance values of the loop ranged from 0.1 KΩ to
50 KΩ. Reading the ADC values is provided either by S2000/S2000M console tools or by UProg Con-
figuration Tool while programming the loop (see Figure 13, the page 75 of this Manual).